MiniCube (G0070980) Guide
Generac Minicube Troubleshooting Guide
Overspeed Warning
- Check the sensor near the flywheel (right side of the generator).
- Crank Sensor Part Number: 0D2244M.
- Check throttle actuator to make sure it moves smoothly.
- Pinpoint test harness from crank sensor to J connector.
- Pin 10 (R15B) on connector J1 is the Overspeed/Watchdog pin
- If the engine RPM falls outside of factory parameters, the watchdog timer will shutdown the engine.
- Inspect throttle actuator play manually and with engine running
Engine surges and doesn’t run great?
- Potential Causes:
- Poor fuel quality
- Loose filter/fuel lines
- Failing injectors
- Failing throttle actuator
- Loose throttle actuator
- Bad governor settings
- Weak lift pump
Overcrank Warning’
- https://talk.newagtalk.com/forums/thread-view.asp?tid=64537 (Remember these generators use off the shelf injection pump, fuel pump and filter housing.)
- Inspect the check valve on top of the tank (G070327) or the filter housing.
- Use the strongest CCA battery possible to ensure faster cranking.
- Add check valve to fuel return too. (This mod may be already present on some generators, especially larger ones.
- Potential Causes:
- Poor fuel quality
- Clogged fuel filter
- Exerciser not set
- Block heater not working
- Weak battery
- Weak starter
- Make sure fuel shutoff solenoid isn’t cracked or leaking.
- Possible Mods:
- Modify the fuel return tube to reach the bottom of the tank to prevent air in the return line.
- Install an electric lift pump wired to the run relay (minimum pressure 10psi and minimum 1 GPM).
- Increase cranking time in GenLink and start attempts
-
Increase number of excercises
Resetting Faults
- General Faults: Unplug the blue connector from the back of the ECM.
- Continuous Circuit Test Faults: Unplug or jump the sensor associated with the fault.
Panel Removal
- Unbolt panels one by one with a 10mm tool until the radiator panel is accessible.
- If the lock won’t unlock or lock: Push inwards on the latch while turning the key.
Fuel pickup tube
- Fuel pickup tube is 48.8cm long
- If OEM one broke, 5/16 brake line works great
- OEM part number is 10000000986
Preventative Maintenance
- Set the generator to exercise weekly to catch faults early.
Bypassing the Factory Charger
- Save the OEM charger connector. It contains all the pins needed to hook up an aftermarket charger.
- Make sure to jump the two alarm pins.
Slow Fuel Gauge
- The fuel gauge consists of a magnetic sensor and float with a lever. It may take time to react to fuel changes.
- When filling quickly, fill to 75% to ensure it doesn’t get overfilled.
Part Numbers with Leading Zeros
- Remove all zeros before the part number before searching.
Coolant Low
- Check the radiator cap, overflow hose, coolant heater and hose connections.
- If no visible leaks are found, the generator may be slowly consuming coolant.
Primer
- Primer won’t come up? Check for clog in line to primer
-
Primer won’t go down? Open bleeder screw on filter housing and try again. Otherwise, there is a clog after the primer.
Fuel Gauge Stuck?
- Sometimes, you can tap on it, but that doesn’t always work.
- Try unbolting the gauge and wedging it out halfway and try to free it up.
-
You can use oil filter pliers to rotate gauge off.
Panel Hard to put on?
- Space out brass mounts with washers
How to fill coolant without taking panels off?
- Use radiator drain valve (above fuel box) and strong enough pump to fill generator.
- Some have an access hatch on roof of generator.
-
You can potentially fill it through overflow tube with pump too.
How to make block heater more servicable?
- Add a 3 wire 6 screw terminal block or outlet to power the block heater
HUIO module location?
- XXX
Common warning tripped but no alarm?
- ????
Battery Chargers Keep Failing
- Check for corrosion and ensure all hot/neutral lugs are tight on the generator and breaker box.
- It’s possible to replace the battery charger with an aftermaket one, and keep the OEM connector.
Generator Runs Around 100 RPM When Switched Off
- Check the fuel shutoff solenoid and throttle actuator.
- Some fuel shutoff solenoids can stick, especially with bad fuel quality.
Windings Smoking When Running
- Advice is currently unavailable for this issue.
Replacing the Coolant Heater
- Remove the first 3 panels
- Close both ball valves to simplify the repair process.
- Prefill the coolant heater to limit the chance of low coolant alarm.
Largest battery possible?
- The dimensions of the battery box is X-X-X and the battery box can fit a Group XX battery if you tip it in there.
Minicube manuals may be more accessible due to being under the G007XXXX series just like the Guardian?